Date First Issued |
10 July 2007 |
Revision Number: |
1.14 |
Revision Date |
14 January 2016
|
Document Information
Document Title: Antenna System Sweep Standard
Document Subject: Antenna Sweep Standard
Document Author: Chad Au, Cheuk Mak
Author’s Manager: Jeff Anderson
Company: T-Mobile USA
Document Category: Antenna System
Document Keywords: Antenna, coaxial cable, TMA, sweep, return loss, distance-to-fault, insertion loss, cable length
Document Comments: Informational Release
Document Web Location : TBD
Date: January 14, 2016
Document Approved:
Document Authorized:
Table of Contents
Antenna System Sweep Standard. 1
Document Title: Antenna System Sweep Standard. 2
Document Subject: Antenna Sweep Standard. 2
Document Author: Chad Au, Cheuk Mak. 2
Author’s Manager: Jeff Anderson. 2
Document Category: Antenna System.. 2
Document Comments: Informational Release. 2
Document Web Location : TBD.. 2
- REVISION INFORMATION.. 5
- INTRODUCTION.. 7
- INTENDED AUDIENCE.. 8
- REFERENCE DOCUMENTS. 9
- BASIS FOR ANTENNA SYSTEM MEASUREMENTS. 10
7.1. Calibration and Equipment Setup. 13
10.1. TMA Gain and Insertion Loss. 18
11.1. Diplexer/Triplexer Insertion Loss. 23
11.2. Diplexer Return Loss. 24
12.1. Main Feeder Line Sweep. 29
12.1.1. Main Line Return Loss Measurement – 50 W Dummy Load. 29
12.1.2. Main Line Path Loss Measurement – Short 30
12.2. System Return Loss Measurement 31
12.3. System Path Loss Measurement 32
12.4. Cable Length Measurement 35
APPENDIX A – Coaxial Cable Spec Summary Table. 38
Coaxial Cable Return Loss/VSWR.. 38
Coaxial Cable Path Loss per 100ft 38
APPENDIX B – Measurement Log Table. 39
APPENDIX C – Example Sweeps. 40
APPENDIX D – Diplexed TMA/Diplexer System Sweep Setup. 44
1. REVISION INFORMATION
Document History
Date |
Author |
Comments |
|
Draft |
29 October 2007 |
Chad Au, Cheuk Mak |
First Draft |
1.0 |
30 October 2007 |
Steve Fischer |
Changed sweep limits to 1700-2100 MHz for path loss and feeder length measurements. |
1.1 |
31 October 2007 |
Mark Lane; Tony Silveira |
Revised text for grammar; define tests for existing and new feeders, use real short rather than simulated where applicable. |
1.2 |
31 October 2007 |
Baljit Singh; Morten Jespersen; Mike Bath |
Spec insertion loss based on cable length; require data in actual logs, not .pdf; cable length Excel file. |
1.3 |
7 November 2007 |
Steve Fischer; Chad Au |
Added Appendix B – Sweep samples; change all sweeps to 1700-2200 MHz. |
1.4 |
12 December 2007 |
Cheuk Mak |
Update doc to a full antenna system sweep standard |
1.5 |
29 October 2008 |
Cheuk Mak |
Updated Appendix B and added Appendix D for As built drawing |
1.6 |
6 November 2008 |
Cheuk Mak |
Updated Sections 8, 9, 10,11, 12 |
1.7 |
7 November 2008 |
Cheuk Mak |
Updated diplexer system sweep |
1.8 |
16 April 2009 |
Chad Au |
Clarify TMA biasing diagrams in Section 10 |
1.9 |
24 April 2009 |
Chad Au |
Add 2-port cal diagram to Sec. 7; diplexed TMA test diagrams to Sec. 10; diplexed system sweep descriptions to Sec. 12.2 and 12.3; typical sweep data to appendix |
1.10;1.11 |
28 February 2014 |
Joe Tseng |
Add 700Mhz TMA/Diplexer test Diagrams; Update requirements for 700Mhz, Inband Diplexer, and Triplexer; Update Mainline testing, coax insertion loss |
1.12 |
30 July 2014 |
Joe Tseng |
Corrected IL for diplexer testing measurement tables and RL for TMA tables, modified antenna PIM photo to further clarify direction of antenna, update TMA and Diplexer 700Mhz devices |
1.13 |
6 Nov 2015 |
Chad Au |
New RL pass/fail criteria for RRU and ground based configurations involving PCS/AWS/700 antennas: Sec. 9, 12 |
1.14 |
14 January 2016 |
Joe Tseng |
Updated IL for diplexer tables with approved solutions, include 700Mhz-only pass/fail sweep criteria. Sect 9,12 remove (RRU site) comment for PCS/AW/700 ant in sec 12 |
2. INTRODUCTION
In order to achieve optimum performance of LTE and UMTS antenna line system, it is essential that all critical components of the network be installed and maintained to the highest standards, within practical means. The antennas, cables, and connectors are constantly exposed to the elements. Any degradation in the antenna system can directly impact the radio link, resulting in call setup failures, handover failures, degraded quality, or dropped calls.
The tests described in the following sections are designed to ensure that the antenna, cable tower mounted amplifier (TMA) and diplexer– if applicable – perform to the required specification prior to integration of the BTS/Node B/eNodeB into the network. For sites already on-air, the tests can be used for trouble shooting problems.
3. INTENDED AUDIENCE
This document is primarily designed for T-Mobile RF directors, senior managers, and engineers. It is assumed that users of this document are familiar with the operation of sweep equipment such as the Anritsu SiteMaster.
4. REFERENCE DOCUMENTS
“Antennas,” Second Edition, J. D. Kraus
Antenna Sweep Standard 10-09-07
Sweep Standard T-Mobile NE Rev 2007
5. BASIS FOR ANTENNA SYSTEM MEASUREMENTS
The functionality of an antenna system, i.e. antenna, feeder & jumper cables, and TMA, is determined by these basic tests, which are based primarily on the impedance of the system:
- VSWR/Return Loss
- DTF (Distance To Fault)
- Insertion Loss
5.1. VSWR/Return Loss
In general, any antenna by itself or connected to a transmission line will produce a reflected wave with reflection coefficient rv and a voltage standing wave ratio (VSWR)1:
Or,
:1 |
VSWR is a unit-less value, because it is a ratio. It is usually expressed as “:1” since the ideal value is referenced to unity.
The efficiency of power transfer from RF source to the load impedance is dependent on how well matched is their impedance (output and load). Therefore, the lower the reflection, the greater is the power transfer. This can also be quantified as return loss (RL):
5.2. DTF
The ability to measure the distance to any discontinuity in impedance along the entire antenna system, i.e. connectors, the antenna, TMA, or kinks in the cable, provide a very useful means for locating connectors, faults, and establishing cable lengths within the system. For test instruments using time domain reflectometry (TDR), a DC pulses and their reflections are used to determine the location of discontinuities. However, for instruments such as the Anritsu SiteMaster, frequency domain reflectometry (FDR) is used instead. In this method, the swept frequency data is mathematically transformed using the inverse FFT (Fast Fourier Transform) operation and presented as time (distance) domain data:
Theoretically, the summation should be performed from –¥ to ¥, but the FDR method spans only a finite frequency band. So, its results are approximated. Also, the coaxial cables at the cell site are typically connected to an antenna, which can receive stray signals from the environment. As such, external signal contributions are mixed in with the actual hardware under test. The ideal FDR DTF measurement should be made with a closed system.
Therefore, the results from this method does not measure actual RF performance and should NOT be used for determining pass/fail of the system according to their specifications, but only to establish a baseline for future reference. It is acceptable to use DTF to locate discontinuities and faults, and establish cable lengths within the antenna system. |
5.3. Path/Insertion Loss
The insertion or cable loss (CL) of an antenna system is the total loss of signal through the coaxial cables and TMA (where applicable). This loss takes away directly from both the UL and DL link budgets. Contributors to this loss include ohmic losses in the conductors, dielectric losses, and mismatch losses at the connectors and any damages along the cables. Typically, the use of a larger diameter cable will lessen some of these effects.
6. SYSTEM CONFIGURATION
The following illustrates the antenna system during sweep tests:
Note: Torque coaxial cable connectors according to manufacturer’s requirements.
7. REQUIRED EQUIPMENT
- Anritsu SiteMaster, or equivalent
- Precision Open, Short, and 50-ohm Load calibration standards
- Phase-stable test cable(s)
- Inter-series adapters for mating between N-type and 7/16 DIN connectors
The Anritsu Site Master S331C is recommended, but the following models can also be used: 235A, S251A/B, S331A/B, MT8222A, or equivalent. Resolution must be set to maximum (typically 512 points) and cannot be below 256 points.
Note: The Anritsu SiteMaster in DTF mode will only measure a maximum cable length of 83 m with 256 points (based on sweep of 2300-2700 MHz and propagation velocity of 0.8). Use of 512 points is recommended.
Number of data points (Resolution) |
512 (or the maximum setting for the instrument) |
RL, CL and DTF Tests |
CW OFF |
The Anritsu Site Master shall be warmed up for at least 15 minutes prior to conducting any test and then calibrated. The Site Master shall also be calibrated each time it is powered up. If the temperature icon indicates excessive ambient temperature, it shall be re-calibrated.
Ensure all cables and jumpers under test are in their permanent locations and anchored positions. Hangers, cable blocks, ground kits, and other hardware must be in place and connected using industry-standard torque wrenches to meet specifications for connectors.
7.1. Calibration and Equipment Setup
Before making any measurements, the test equipment shall be allowed to stabilize for a period of approximately 15 minutes and calibrated for 1-port return loss measurements using a phase stable cable, precision 50 ohm load, open, and short circuit terminations (Figure 1a), or 2-port insertion loss/gain measurements (Figure 1b), as appropriate. Detailed examples of how to setup and calibrate Anritsu equipment can be found in Appendix A. NOTE: Equipment must be calibrated per manufacturer suggested calibration period.
Note: The Anritsu SiteMaster will not detect when a short is erroneously connected when the prompt is for an open and vice versa, resulting in a faulty calibration, and thus, invalid measurements.
Note: When changing measurements from mid-band (PCS and AWS) to low-band spectrum (700 MHz), calibration of the sweep equipment will be required for the new measured band. Inversely when changing measurements from low-land (700 MHz) to mid-band (PCS and AWS) spectrum, calibration of the sweep equipment will be required for the new measured band.
Figure 1a Anritsu SiteMaster 1-Port Calibration Setup
Figure 1b Anritsu SiteMaster 2-Port Calibration Setup
8. Sweep Requirement
The Section below will describe T-Mobile Sweep requirement:
- Antenna Quality Sweeps (On Site)
- TMA Quality Sweeps (On Site)
- Diplexer Quality Sweeps (On Site) if applicable
- Main Feeder Line Sweeps
- Antenna System Sweeps
9. QUALITY OF ANTENNAS (On Site)
It is recommended that sweep tests are done by antenna line GC on site before installation. The quality of the impedance match to 50-ohms at the antenna connectors is determined. This test is performed with the SiteMaster calibrated for a one-port return loss measurement to the end of the test cable. With the N-type connector on the test cable and calibration kit, an N-DIN adapter has to be inserted to allow mating of the test cable to the antenna. Ensure that the antenna is positioned face-up (Figure 2) towards the sky at least 24” above the ground and away from metallic structure or equipment, e.g. not inside shelter or under ice bridge, set it on a non-metallic fixture such as a trash can.
- Configure the test equipment in return loss mode and calibrate per Section 7.
- Set antenna RET to 0° for worst case
- Identify if the antenna passes or fails.
- Save the trace for printing. This shall include site and sector numbers for identification.
A copy of each trace shall be attached to the antenna sweep checklist so that the RF Engineer can inspect and sign off acceptable results.
Figure 2 Antenna Test with SiteMaster
Sweep Test Frequency Range |
698 – 746 MHz; 1710 – 2155 MHz (Note: Antenna port dependent) |
Vertical Axis |
0 dB to -40 dB |
700 MHz RL Sweep Limits |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Antenna Return Loss – standalone |
· All antenna ports are tested to determine RL is within specifications. · RL ≤ –16 dB (VSWR <= 1.4:1) for variable tilt PCS/AWS and 700-only antenna · RL ≤ –14 dB (VSWR <= 1.5:1) for variable tilt PCS/AWS/700 antenna · RL ≤ –18 dB (VSWR <= 1.3:1) for fixed tilt antenna |
Save sweeps as (1 sweep per ANT port) – See Ch 13 |
1. SiteID_ColorCode_ ANT####_ RL_P#_???_Date (All frequency bands applicable need to measured) ANT#### = ANT last 4 digits of the serial # P# = Antenna Port number ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
10. QUALITY OF TMA (On Site)
10.1. TMA Gain and Insertion Loss
It is recommended that sweep tests are done by antenna line GC on site before installation. For TMA’s not yet integrated into the antenna system, this shall be the method of verifying TMA gain. A two-port test device, such as an Anritsu SiteMaster S251A or Agilent Network Analyzer is required. The test gear is used to generate a sweep signal into the antenna port of the TMA. This signal then emerges at the BTS port and is measured by the input port of the test equipment, with gain in the receive band.
- Calibrate per Sec. 7 the instrument with two test cables for a two-port “Thru” measurement for gain test.
- TMA must be biased through the internal DC source of the Site Master or +12Vdc from other DC source when TMA is tested through each channel.
- Note that TMA equipment under test must be labeled and identified by the sector where they are to be installed.
Figure 3a Dual Band or Twin TMA Gain Test with SiteMaster; be sure the TMA is turned on either with internal or external 12VDC bias, respectively.
Figure 3a Diplexed TMA Gain Test with SiteMaster; be sure the TMA is turned on either with internal or external 12VDC bias, respectively.
TMA Gain – standalone |
Determines the Gain of the TMA. Pass/Fail limit is 12 ± 1 dB; 1850 – 1910 MHz; 1710 – 1755 MHz Both paths of TMA are measured |
TMA Tx Band Insertion Loss |
Pass/Fail limits: ≤ 0.5 dB for TMA only; 1930 – 1990 MHz, 2110 – 2155 MHz Pass/Fail limit: ≤ 0.3 dB for 700 MHz bypass where applicable; 698 – 746 MHz *Value based on the table 1 in section 11 listed below; if diplexer is installed, add the insertion of the diplexer to the TMA |
Sweep Test Frequency Range |
698 – 746 MHz; 1710 – 2155 MHz |
700 MHz IL Sweep (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS IL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS IL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Save Sweep as (1 sweep per BTS port) – See Ch 13 |
“SiteID_ColorCode_TMA####_GAIN_P#_???_Date” (All frequency bands applicable need to measured) TMA#### = TMA last 4 digits of the serial # P# = Port number as marked in TMA ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
10.2. TMA Return Loss
- Configure the test equipment in return loss mode and calibrate per Sec. 7.
- TMA must be biased through the internal DC source of the Site Master or +12Vdc from other DC source when TMA is tested.
- Identify if the TMA passes or fails.
- Save the trace for printing. This shall include site and sector numbers for identification.
- Note that equipment must be labeled with mark of the sector where they belong.
Figure 4a Dual Band or Twin TMA Return Loss Test with SiteMaster, with internal and external bias, respectively. Be sure to use 50 ohm load
Figure 4b Diplexed TMA Return Loss Test with SiteMaster, with internal and external bias, respectively. Be sure to use 50 ohm load
TMA Return Loss (RL) – standalone |
Determines the Return Loss of the TMA. Pass/fail limit is =< -18dB on Marker 5 and 6 The RL of all TMA connectors are measured. |
Overall Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
700 MHz RL Sweep (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Save Sweep as (1 per ANT port and 1 per BTS port) – See Ch 13 |
1. SiteID_ColorCode_TMA####_RL_BTS#_???_Date (All frequency bands applicable need to measured) 2. SiteID_ColorCode_TMA####_RL_ANT#_???_Date (All bands applicable need to measured) TMA#### = TMA last 4 digits of the serial number BTS# = BTS Port number as marked in TMA ANT# = ANT Port number as marked in TMA ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
11. QUALITY OF Diplexer (On Site)
11.1. Diplexer/Triplexer Insertion Loss
It is recommended that sweep tests are done by antenna line crew on site before installation. For diplexers and triplexers not yet integrated into the antenna system, this shall be the method of verifying their insertion loss. A two-port test device, such as an Anritsu SiteMaster S251A, Agilent Network Analyzer, or equivalent is required. The test gear is used to generate a sweep signal into the antenna port of the TMA. This signal then emerges at the BTS port and is measured by the input port of the test equipment, with gain in the receive band. Calibrate the instrument with the two test cables for a two-port “Thru” measurement for gain test.
- Terminate all ports not being swept with 50 Ω
- Note that equipment under test must be labeled with mark of the sector where they belong.
Figure 5 Diplexers and Triplexer insertion loss test with SiteMaster
Diplexer Insertion Loss |
Determines the Insertion Loss of the diplexer. 700, AWS, PCS value should be based on those found in Table 1. |
Overall Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
700 MHz IL Sweep (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS IL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS IL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Save Sweep as (1 sweep per BTS port) – See Ch 13 |
1. SiteID_ColorCode_DLR####_IL_???_Date (All frequency bands applicable need to measured) DLR#### = TMA last 4 digits of the serial # P# = Port number as marked in TMA ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
11.2. Diplexer Return Loss
- Configure the test equipment in return loss mode and calibrate.
- Identify if the diplexer passes or fails.
- Save the trace for printing. This shall include site and sector numbers for identification.
- Note that equipment must be labeled with mark of the sector where they belong.
Figure 6. Diplexer Return Loss Test with SiteMaster, be sure to use 50 ohm load
TMA Return Loss (RL) – standalone (applied over sweep limits) |
Determines the Return Loss of the diplexer. Pass/fail limit is =< -18dB on Marker 5 and 6 The RL of all TMA connectors are measured. |
Overall Sweep Test Frequency Range |
698-746 MHz;1700 - 2165 MHz |
700 MHz RL Sweep (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Save Sweep as (1 per BTS and 1 per ANT port) – See Ch 13 |
1. SiteID_ColorCode_DLR####_RL_???_Date (All frequency bands applicable need to measured) 2.SiteID_ColorCode_DLR####_RL_ANT_???_Date (All frequency bands applicable need to measured) DLR#### = TMA last 4 digits of the serial number ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
Make |
Type |
Model |
Insertion Loss, Max, (dB) |
CommScope |
Dualband AWS port |
E15S08P78 |
0.3 |
CommScope |
Dualband PCS port |
E15S08P78 |
0.7 |
CommScope |
Twin AWS |
E15S08P80 |
0.3 |
CommScope |
Twin PCS |
E15S09P99 |
0.7 |
CommScope |
Bias Tee |
ABT-DFDM-ADB |
0.1 |
CommScope |
Smart Bias Tee |
ATBT-S5xx |
0.1 |
CommScope |
Diplexer DC Switching |
ECC1920-VPUB |
0.3 (AWS) 0.3 (PCS) |
RFS |
Dual band AWS port |
ATMAP1412D-1A20 |
0.4 |
RFS |
Dual band PCS port |
ATMAP1412D-1A20 |
0.6 |
RFS |
Twin AWS |
ATMAA1412D-1A20 |
0.4 |
CommScope |
AWS In-Band Diplexer |
D-AWS-10-A-CDEF, D-AWS-10-B2C-F, D-AWS-10-B-EF |
0.5 |
CommScope |
AWS 5M gb In-Band Diplexer |
TD-AWS-5-ABC-EF[1], TD-AWS-5-ABCD-F[2], TD-AWS-5-AB-DEF1[3]
|
0.8 |
CommScope |
PCS In-Band Diplexer |
TD-PCS-5-A-B_C, TD-PCS-5-A4_D-B4_C, , TD-PCS-5-B-FC, TD-PCS-5-B4_E-C |
0.7 |
CCI |
AWS 0M GB In-Band Diplexer |
LLC-1721-FTU-0-F1F2, LLC-1721-FTU-0-A1A2, LLC-1721-FTU-0-CD |
0.7[4] |
Commscope |
Mid band TMA w/ 700M bypass (Style 3C) |
TMAT1921B78-31-A |
0.3 (AWS) 0.5 (PCS) 0.2 (700 MHz) |
Commscope |
Diplexed AWS+700 ABC TMA (Style 3D) |
TMAS7LABC21-210A |
0.2 (AWS) 0.3 (700 MHz) |
RFS |
Twin 700 TMA |
ATM700LD-1A20 |
0.3 |
Commscope |
Twin Mid band/700 Diplexer |
CDX723AT-DS (E15V95P46) |
0.15 (AWS/PCS) 0.15 (700 MHz) |
Commscope |
Twin Multiband Triplexer |
CBC61921x-DS-2X |
0.3 (AWS/PCS) 0.2 (700 MHz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 1 Insertion Loss Limits of various TMA’s, diplexers, and triplexer
12. ANTENNA SYSTEM SWEEPS
The following sweep tests must be completed before the site can be approved. The traditional ground based site configuration has an antenna system consisting of antenna, antenna jumper, LNA (operating in the on-mode), LNA jumpers, and main feeder. However, with more and more sites having remote radio units (RRU) deployed close to the antennas via hybrid cable, those antenna systems consist of merely a short jumper cable and the antenna itself. Therefore, the term “main feeder” below is a generalized description to mean either the main coax cable at a traditional ground base site, or just the jumper cable between the radio head and the antenna for an RRU site.
Note: All data shall be recorded in raw data logs, and not Adobe Acrobat “pdf” format or .jpg, to allow further post processing.
[Note: File naming convention is a suggestion and naming should follow National Operations standards.]
Main Feeder Sweeps
- Main Feeder Return Loss Measurement with Load (12.1.1)
- Main Feeder Return Loss Measurement with Short (12.1.2)
System Sweeps
- System Return Loss Measurement (12.2; for system sweep diagram for system with diplexer refer to Appendix D) with Antenna
- System Path Loss Measurement (12.3)
- System Distance to Fault cable length (can also be obtain by converting 12.3 path loss into “DTF”) measurement (12.4)
12.1. Main Feeder Line Sweep
The following set of tests shall be performed for the main feeder line
12.1.1. Main Line Return Loss Measurement – 50 W Dummy Load
Perform measurement with 50 ohm dummy load connected at tower top end of cable.
Figure 7 50 ohm dummy load connected at tower top end of cable.
Overall Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
700 MHz RL Sweep Limits (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Vertical Axis |
0 dB to -40 dB |
Pass/Fail Limit (applied over sweep limits) |
≤ -24 dB with 50 ohm dummy load connected |
Save Whole System Test As (1 sweep per line) – See Ch 13 |
“SiteID_ColorCode_MLRL_???_Date” (All frequency bands applicable need to measured) ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
12.1.2. Main Line Path Loss Measurement – Short
Perform measurement with short circuit terminator connected at tower top end of cable. Return loss value must be divided by 2 to result in true path loss.
Figure 8 Short circuit terminator connected at tower top end of cable.
700 MHz RL Sweep Limits (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Vertical Axis |
0dB to -40dB |
Main Feeder |
With short circuit terminator |
Total System Pass/Fail Limit |
(Use spreadsheet in Appendix for particular cable type’s expected insertion loss criteria) |
Save Whole System Test As (1 sweep per line) – See Ch 13 |
“SiteID_ColorCode_MLPL_???_Date” in Site Master (All frequency bands applicable need to measured)
??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
12.2. System Return Loss Measurement
The impedance measurement of an antenna system with a TMA installed will be assessed through the feeder, the impedance of the LNA output stage for the Rx band, and the Tx filter characteristics. For diplexed configurations where the main feeder is shared between 2G and 3G base stations, the diplexer is then part of the system and shall be included in the measurement.
Note: For the exception case where RFS TMA’s without bypass are involved, the return loss criteria at the UL band of 1710-1755 MHz do not apply.
Figure 9 System sweep include antenna, antenna jumper, TMA (if used), TMA jumper, feeder cable, diplexer (if used), and cabinet jumper
Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
700 MHz RL Sweep Limits (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Vertical Axis |
0 dB to -40 dB |
Total System |
Feeder Cable, Diplexer (if used), TMA Jumper Cable, TMA (if used), Antenna Jumper Cable, Antenna *Refer to Appendix D for system with diplexer |
Total System Pass/Fail Limit (applied over sweep limits) |
≤ -18 dB with fixed tilt PCS/AWS antenna ≤ -16 dB with fixed tilt PCS/AWS antenna with TMA (ON) ≤ -14 dB (VSWR <= 1.5:1) for variable tilt PCS/AWS/700 antenna ≤ -16 dB with variable tilt PCS/AWS and 700-only antenna ≤ -16 dB with variable tilt PCS/AWS and 700-only antenna with TMA (ON) |
Save Whole System Test Log As – See Ch 13 |
“SiteID_ColorCode_SRL_???_Date” (All frequency bands applicable need to measured) ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
12.3. System Path Loss Measurement
As tower work is performed to install or swap antennas and/or TMA’s, the installer shall attach a short circuit termination for this measurement, which is the required method. For diplexed configurations where the main feeder is shared between 2G and 3G base stations, the diplexer is then part of the
system and shall be included in the measurement.
Return loss value must be divided by 2 to result in true path loss.
Figure 10a System sweep include short circuit termination, antenna jumper, TMA (if used), TMA jumper, feeder cable, and cabinet jumper
Figure 10b System sweep include short circuit termination, antenna jumper, TMA (if used), TMA jumper, feeder cable, diplexer (if used) and cabinet jumper
Overall Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
700 MHz RL Sweep Limits (where applicable) |
UL: 698 MHz – 716 MHz DL: 728 MHz – 746 MHz Markers @: Max Peak 698 – 716 MHz, Max Peak 728 – 746 MHz |
AWS RL Sweep Limits |
UL: 1710 MHz –1755 MHz DL: 2110 MHz – 2155 MHz Markers @: Max Peak 1710 – 1755 MHz, Max Peak 2110 – 2155 MHz |
PCS RL Sweep Limits |
UL: 1850 MHz – 1910 MHz DL: 1930 MHz – 1990 MHz Markers @: Max Peak 1850 – 1910 MHz, Max Peak 1930 – 1990 MHz |
Vertical Axis |
0dB to -40dB |
Total System |
Feeder Cable, Diplexer (if used), TMA Jumper cable, TMA (if used), Antenna Jumper Cable, Antenna *Refer to Appendix D for system with diplexer |
Total System Pass/Fail Limit |
(Use spreadsheet in Appendix A for particular cable type’s expected insertion loss criteria) +/- 5% from the calculated value on Marker 3 |
Save Whole System Test Log As – See Ch 13 |
“SiteID_ColorCode_SPL_???_Date” (All frequency bands applicable need to measured) ??? = Frequency band being measured (AWS, PCS, and 700) |
12.4. Cable Length Measurement
A close approximation of the coaxial length can be obtained without the need for a short-circuit termination at the tower top. From the measurement taken from Sec. 10.1.2, the Anritsu SiteMaster can convert the Return Loss measurement to a Distance-To-Fault (DTF) measurement, thereby providing the length of the feeder cable.
[Note: File naming convention is a suggestion and naming should follow National Operations standards.]
Overall Sweep Frequency Range |
698-746 MHz;1710 - 2155 MHz |
Markers |
Marker 1: Max Peak (meters) |
Vertical Axis |
0dB to -40dB |
Horizontal Axis |
0m to 150m |
Total System |
Feeder Cable, Diplexer (if used) TMA Jumper cable, TMA (if used), Antenna Jumper Cable, Antenna *Refer to Appendix D for system with diplexer |
Total System Pass/Fail Limit |
Within 0.5m of the other feeder cable length |
Save Whole System Test Log As – See Chapter 13 |
“SiteID_ColorCode_DTF_???_Date” ??? = Frequency band being measured (AWS, PCS, and 700) [Note: File naming convention is a suggestion and naming should follow National Operations standards.] |
13. Data Format
- [Note: File naming convention is a suggestion and naming should follow National Operations standards.]
- Each sweep measurement data trace shall be clearly labeled BEFORE the test is performed with:
- Site ID
- ColorCode (i.e. red, red, white = RRW)
- Type of measurement (i.e. system return loss = SRL)
- Frequency band of sweep [?B = MB for mid-band (AWS/PCS) and LB for low-band (700Mhz)]
- Date (i.e. November 6, 2008 = 110608)
- All Sweep measurement must be save in format that can be open with notepad or MS excel for analysis
- All Sweeps for a site be saved under one folder that name “Site ID” (i.e. SEA012345)
- All Measurement log must be save in the same folder with name “SiteID_MeaLog_Date
11 Contact List
Name |
Position/Department |
Contact Number |
|
Chad Au |
Principal Engineer, SystDesign& Strategy, Technology |
425-748-3121 |
Chad.Au@t-mobile.com |
Joe Tseng |
Sr Engineer, SystDesign & Strategy, Technology |
425-383-2689 |
Joe.Tseng@t-mobile.com |
Jeff Anderson |
Sr Manager, Systems Design & Strategy, Technology |
425-344-0011 |
Jeff.Anderson@t-mobile.com |
APPENDIX A – Coaxial Cable Spec Summary Table
Coaxial Cable Return Loss/VSWR
Make |
Cable |
Model |
Return Loss |
VSWR (max.) |
CommScope |
7/8” Heliax |
LDF5-50A |
-24.5 dB |
1.13:1 |
CommScope |
1-1/4” Heliax |
LDF6-50A |
-24.5 dB |
1.13:1 |
CommScope |
1-5/8” Heliax |
LDF7-50A |
-24.5 dB |
1.13:1 |
CommScope |
2-1/4” Heliax |
LDF12-50 |
-24.5 dB |
1.13:1 |
CommScope |
7/8” Virtual Air |
AVA5-50 |
-24.5 dB |
1.13:1 |
CommScope |
1-1/4” Virtual Air |
AVA6-50 |
-24.3 dB |
1.13:1 |
CommScope |
1-5/8” Virtual Air |
AVA7-50 |
-24.5 dB |
1.13:1 |
CommScope |
1-1/4” Aluminum |
FXL 140-1 |
-26.4 dB |
1.10:1 |
CommScope |
1-5/8” Aluminum |
FXL 1873 |
-26.4 dB |
1.10:1 |
RFS |
7/8” Premium |
LCF78-50JA-A5 |
-24.0 dB |
1.135:1 |
RFS |
1-1/4” Premium |
LCF114-50JA-A5 |
-24.0 dB |
1.135:1 |
RFS |
1-5/8” Premium |
LCF158-50JA-A5 |
-24.0 dB |
1.135:1 |
RFS |
7/8” Standard |
LCF78-50 |
-24.0 dB |
1.135:1 |
RFS |
1-5/8” Standard |
LCF158-50 |
-24.0 dB |
1.135:1 |
Eupen |
7/8” Standard |
EC5-50 |
-24.5 dB |
1.13:1 |
Eupen |
1-1/4” Standard |
EC7-50 |
-24.5 dB |
1.13:1 |
Eupen |
1-5/8” Standard |
EC12-50 |
-24.5 dB |
1.13:1 |
All |
Existing Coaxial Feeder |
All |
-22.0 dB |
1.17:1 |
Coaxial Cable Path Loss per 100ft
Make |
Cable |
Model |
Velocity |
Loss/100’ |
|
@2 GHz |
@700 MHz |
||||
CommScope |
½” Heliax |
LDF4-50A |
0.88 |
3.25 dB |
1.83 dB |
CommScope |
½” SuperFlex |
FSJ4-50B |
0.81 |
5.37 dB |
2.95 dB |
CommScope |
7/8” Heliax |
LDF5-50A |
0.89 |
1.86 dB |
1.03 dB |
CommScope |
1-1/4” Heliax |
LDF6-50A |
0.89 |
1.35 dB |
0.73 dB |
CommScope |
1-5/8” Heliax |
LDF7-50A |
0.88 |
1.13 dB |
0.60 dB |
CommScope |
2-1/4” Heliax |
LDF12-50 |
0.88 |
0.99 dB |
0.52 dB |
CommScope |
7/8” Virtual Air |
AVA5-50 |
0.91 |
1.76 dB |
0.99 dB |
CommScope |
1-1/4” Virtual Air |
AVA6-50 |
0.92 |
1.25 dB |
0.71 dB |
CommScope |
1-5/8” Virtual Air |
AVA7-50 |
0.92 |
1.02 dB |
0.56 dB |
CommScope |
1-1/4” Aluminum |
FXL 1480 |
0.89 |
1.24 dB |
0.69 dB |
CommScope |
1-5/8” Aluminum |
FXL-1873 |
0.88 |
1.02 dB |
0.55 dB |
RFS |
½” CellFlex |
LCF12-50J |
0.88 |
3.20 dB |
1.81 dB |
RFS |
½” SuperFlex |
SCF12-50J |
0.88 |
4.82 dB |
2.82 dB |
RFS |
7/8” CellFlex Premium |
LCF78-50JA-A5 |
0.90 |
1.68 dB |
0.95 dB |
RFS |
1-5/8” CellFlex Prem |
LCF158-50JA-A5 |
0.90 |
1.02 dB |
0.76 dB |
RFS |
2-1/4” CellFlex Prem |
LCF214-50 |
0.88 |
1.05 dB |
0.56 dB |
Eupen |
½” Standard |
EC4-50A |
0.88 |
3.25 dB |
1.83 dB |
Eupen |
½” HiFlex |
EC4-50-HF |
0.88 |
4.90 dB |
2.70 dB |
Eupen |
7/8” Standard |
EC5-50A |
0.88 |
1.71 dB |
0.96 dB |
Eupen |
1-5/8” Standard |
EC7-50A |
0.88 |
1.05 dB |
0.61 dB |
APPENDIX B – Measurement Log Table
APPENDIX C – Example Sweeps
Return Loss for antenna system with no TMA:
Diplexed antenna system with TMA, PCS path:
Diplexed antenna system with TMA, AWS path:
Cable Path Loss, with short connected at top of TMA jumper:
Cable Length:
APPENDIX D – Diplexed TMA/Diplexer System Sweep Setup
Return Loss Sweep Setup
[1] Unit still in validation
[2] Unit still in validation
[3] Unit still in validation
[4] To maintain a balance between narrow guard band and isolation, the IL (insertion loss) at the band edges of the filter are not ideal. Expect the IL to be between .7 to 1.5 dB within 1 MHz of the band edges of the filter for the Zero Guard band models. The IL within the main portion (portion between beyond the 1Mhz of the band edge) of the filter should be or exceed 0.7 dB.